AMPROBE ACD-41PQ

El precio original era: S/3.095,00.El precio actual es: S/1.610,00.

Stock Disponible5 Unidades Disponibles
+ -

AMPROBE ACD-41PQ STOCK DISPONIBLE



PINZA – > MARCA: AMPROBE -> MODELO: ACD-41PQ ; REALIZAMOS ENVIOS A TODO EL PERU AMPROBE ENTREGA INMEDIATA


ACD-41PQ
1000A Power Quality Clampon with THD Measurement
The ACD-41PQ provides a simple and effective way to verify
if the electrical system is affected by harmonics. Enhanced
troubleshooting capabilities with the Power analysis functions.
Increase your ability analyze the data with an optional PC
interface kit.
■ TRMS sensing
■ Measurements: Total Harmonics Distortion THD, AC/DC
Voltage up to 600V, AC Current up to 1000A, Resistance,
Frequency, Temperature
■ ACD-41PQ also measures Active (W), Reactive (VAR) and
Apparent (VA) Power with dual-display Power Factor
readout
■ AutoTect™ – Auto Selection of AC Volts, DC Volts or AC
Amps
■ Total Harmonic Distortion to 51st harmonic
■ Optional PC interface capability
■ Audible continuity
■ Auto power off
■ Automatic polarity
■ Low battery indication
■ Peak hold
■ Data hold
■ Large, easy to read LCD display with backlight
■ Accommodates conductors up to 1.77” (45mm) in
diameter
■ Carrying case, test leads, batteries (installed),
thermocouple and manual included
■ Voltage overload protection for all functions up to 600V

ACD-41PQ 1000A Power Quality Clamp-on with THD Measurement Data Sheet
Specifications (valid for 23 °C ± 5 °C, for less than 70 % relative humidity).
Display
Voltage functions 6000 counts LCD display(s)
Power, Ohm & Hz functions 9999 counts LCD display(s)
ACA clamp-on function 4000 counts LCD display(s)
Update Rate Power function 1 per second nominal
Voltage, ACA clamp-on, Ohm, Hz &
Temperature functions 4 per second nominal
Polarity Automatic
Operating Temperature 0°C to 40°C; < 80% RH @ < 31°C; decreasing linearly to 50% RH @ 40°C Altitude Indoor operation, below 2000m. Storage Temperature -20°C to 60°C, < 80% R.H. (with battery removed) Temperature Coefficient nominal 0.15 x (specified accuracy)/ °C @ (0°C -18°C or 28°C -40°C) Sensing True RMS sensing Power Supply standard 1.5V AAA Size (NEDA 24A or IEC LR03) battery X 2 Low Battery Below approx. 2.4V Power Consumption Voltage, ACA, Hz & Power functions 10mA typical Ohm & Temperature functions 4mA typical APO Timing Idle for 17 minutes APO Consumption 10μA typical Jaw opening & Conductor diameter 45mm max Dimension 224 x 78mm x 40mm (8.9 x 3.1 x 1.6 in.) Weight 224 gm approx Safety LVD Meets EN60101-1:2001; EN61010-2-032(2002), Category III- 600 Volts ac & dc; pollution degree : 2 � EMC EN 61326-1 Electrical Specifications AC Voltage Voltage Range Accuracy 600.0V 50Hz to 60Hz ± (0.5% rdg + 5d) 45 to 50Hz, 60 to 500Hz ± (1.5% rdg + 5d) 500Hz to 3.1kHz ± (2.5% rdg + 5d) CMRR > 60 dB @ DC to 60 Hz, Rs = 1 kΩ
Input Impedance 2 MΩ, 30 pF nominal
Crest Factor < 2.3 : 1 at full scale; < 4.6 : 1 at half scale ACV AutoTechTM Threshold 30VAC (40 to 500 Hz) nominal DC Voltage Range 600.0 V Accuracy ± (0.5% rdg + 5d) NMRR > 50 dB @ 50/60 Hz
CMRR >120 dB @ DC, 50/60 Hz, Rs
VIDEO REFERENCIAL: